up: embedded systems - bacnet - object types  
embedded systems - bacnet - Analog Input propertiesWhat links here?
IndexIdentifierRequiredExample
tablerowObject_IdentifierYesAnalog Input #1
77Object_NameYes"AI 01"
tablerowObject_TypeYesAnalog Input
85Present_ValueYes68.0
tablerowDescriptionNo"Outside Air Temperature"
tablerowDevice_TypeNo"10k Thermistor"
111Status_FlagsYesIn_Alarm, Fault, Overridden, Out_Of_Service flags
36Event_StateYesNormal (plus various problem-reporting states)
tablerowReliabilityNoNo_Fault_Detected (plus various fault conditions)
81Out_Of_ServiceYesFalse
tablerowUpdate_IntervalNo1.00 (seconds)
tablerowUnitsYesDegrees-Fahrenheit
tablerowMin_Pres_ValueNo-100.0, minimum reliably read value
tablerowMax_Pres_ValueNo+300.0, maximum reliably read value
tablerowResolutionNo0.1
tablerowCOV_IncrementNoNotify if Present_Value changes by increment: 0.5
tablerowTime_DelayNoSeconds to wait before detecting out-of-range: 5
tablerowNotification_ClassNoSend COV notification to Notification Class Object: 2
tablerowHigh_LimitNo+215.0, Upper normal range
tablerowLow_LimitNo-45.0, Lower normal range
tablerowDeadbandNo0.1
tablerowLimit_EnableNoEnable High-limit-reporting, Low-limit-reporting.
tablerowEvent_EnableNoEnable To_Offnormal, To_Fault, To_Normal change reporting.
tablerowAcked_TransitionsNoFlags indicating received acknowledgments for above changes.
tablerowNotify_TypeNoEvents or Alarms
embedded systems - bacnet - Analog Input properties
filename:embedded systems - bacnet - Analog Input properties
filename:embedded%20systems%20%2D%20bacnet%20%2D%20Analog%20Input%20properties
last edit:June 24 2015 20:02:07 (3238 days ago)
ct = 1714954527.000000 = May 05 2024 20:15:27
ft = 1435190527.000000 = June 24 2015 20:02:07
dt = 279764000.000000